Sounder beacon red with white Flasher | ROLP-R-LX-W-WF | BOSCH
Product Name | Sounder beacon red with white Flasher | ROLP-R-LX-W-WF | BOSCH |
---|---|
Weight | 1.000000 |
COUNTRY OF MANUFACTURE | India |
Brand | Bosch |
HSN Code | 9403 |
System Type | CONVENTIONAL |
Model | ROLP-R-LX-W-WF |
Freight | To pay by Customer, extra at actuals. Godown Delivery |
Category | Alarm System, Fire Safety, Sounder Beacons |
Product Code | CPK-0133 |
LX Sounder Beacons Conventional
• Complies with EN54-3 and EN54-23
• Up to 7.5 m coverage / DIN tone 102 dB(A)
• Variable flash rate
• Low current consumption
• LED technology
The LX Sounder Beacons are for dual use applications where a visual alarm device is required in addition to an audible alarm.
The device has a unique lens design to achieve the required illumination specified by EN54-23. The flash rate as well as a reduced coverage volume can be set via DIP switch.
The light is distributed in a cubical shape for wall application.
The integrated sound transducer offers a selection of 32 ton variants, including various wailing tones,diverse signals for fire alarm (e. g. the DIN tone according to DIN 33404) and other special modulations.
The tones and volume are set with a 6-pin DIP switch in the signaling device. With a selected tone type, on activation of the second input, the second tone type is switched on.
Depending on the tone type, volume set, and operating voltage, the sound pressure varies. The device is designed for a variety of applications.
Certifications and approvals
Region | Certification | |
Germany | VdS |
G 214070 LX Sounder Beacon Wall Base |
Europe | CE | RoLP LX Wall Base |
CPD | 0333-CPD-075444 LX_Bea- con_Wall_Base_EN |
|
Poland | CNBOP | 2233/2014 ROLP |
Installation/configuration notes
• The current consumption depends on the tone type of the audible device and the flash rate and the coverage of the optical signaling device. Add up both current consumption values to calculate the total
current consumption of the sounder beacon.
• Can be connected to the following fire panels:– FPA-5000 / FPA- 1200 with NZM 0002 A or FLM-420-NAC
– FPC-500 Conventional Fire Panel
•The device is suitable for wall applications.
• The device is suitable for indoor and outdoor use.Outdoor use only with appropriate cable fittings. Not included in delivery.)
• The coverage of the device depends on the ambient
light level. Consider also the maximum mounting height of the device
• For reliable planning use the Planning Software by
Bosch for Fire Alarm Systems.
Parts included
Qty. | Components |
1 | Optical signaling device for wall application, red or white, red flash or white flash (base) |
1 | Audible signaling device, red or white |
Technical specifications | |
Housing and base color |
Red similar to RAL 3031 White similar to RAL 9003 |
Weight | 200 g |
Dimensions (Ø x H x D) |
95 mm x 135 mm x 95 mm |
Operating voltage | 18 - 30 V DC / 9 - 15 V DC |
Current consumption | dependent on flash rate setting, coverage setting and sounder setting |
Environmental conditions | |
Protection class | IP65 * |
Permissible operating temperature |
-25oC - +70oC |
Permissible rel. humidity |
Complies with EN54-23 |
*Manufacturers specification, not third party verified | |
Special features | |
Maximum mounting height (x) |
2.4 m |
Coverage (y) | 7.5 m (switchable to 2.5 m) |
Coverage volume | 135 m3 (15 m3) |
Coverage volume code (C-x-y / W-x-y) |
(C-x-y / W-x-y) W-2.4-7.5 |
Flash rate | 1Hz (switchable to 0.5 Hz) |
Flash color | Flash color |
Maximum sound pressure level |
112 dB(A) |
Current Consumption
Operating Voltage | High power 1 Hz |
High power 0.5 Hz |
Low power 1 Hz |
Low power 0.5 Hz |
|
Coverage | 7.5 m (135 m3) | 2.5 m (15 m3) | |||
White flash | 24 V DC | 25 mA | 16 mA | 16 mA | 10 mA |
Red flash | 24 V DC | 25 mA | 16 mA | 16 mA | 16 mA |
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping & Delivery Policy: |
1. | 100 INR will be charged as shipping fee if buyer and seller are from same city. If Buyer and Seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |
3. | Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis |
4. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |