MPR-341-2C Selec Digital Panel Mount Motor Protection Relay, 2 x 1C/O, 85 to 270V AC / DC
₹1,400.05 ₹1,652.06
In stock
Product Name | MPR-341-2C Selec Digital Panel Mount Motor Protection Relay, 2 x 1C/O, 85 to 270V AC / DC |
---|---|
Weight | 1.000000 |
Brand | Selec |
Test Certificate | Yes |
COUNTRY OF MANUFACTURE | India |
HSN Code | 85363000 |
Warranty | 6 Months |
Shipping time (business days) | 3 |
Freight | To pay by Customer, extra at actuals |
Category | Electrical, Electrical Measurement, Motor & Pump Protection Relay |
Product Code | MPR-341-2 |
In Stock ( 100 Units )
MPR-341-2C Selec Digital Panel Mount Motor Protection Relay, 2 x 1C/O, 85 to 270V AC / DC
Product Description
- Monitors: Phase loss, Phase unbalance, Phase sequence, Overload trip current, Under / Over current in 3Ø motors.
- Accuracy : 5% of set value.
- 2 C/O output relay.
- Auto / Remote test available.
- MPCT range : 10A - 80A
- Earth Fault Current Measurement with EFCT : 1A to 160A
- Aux supply : 90 - 270V AC / DC
Measuring Parameter | Monitors Over Load (As per NEMA Curve), Over Current, Under Current, Earth Fault, Lock Current, Current Asymmetry, Phase Sequence, Phase Failure |
Electrical Connection | 3Ø - 3W |
Test / Reset | Manual / Auto reset |
No. of LED | 2 |
Voltage Measuring Range | 90V - 270V AC / DC |
Earth Fault Current Measurement with EFCT | 31A to 160A |
Current Measuring Range | 3A - 80A (via external MPCT) |
Power Consumption | 4VA (max) |
Output Contact | Trip 1 C/O Alarm 1 C/O (Programmable as Trip / Alarm), Relay Rating NO 5A@250V AC / 28VDCNC 3A@250V AC / 28VDC |
Accuracy | Time ±5%+100msec Current 5% of IR(Rated Current), Reset Auto / Manual |
Functional Specifications | Over Load NEMA class : Start with OFF then Curve 5, 10, 15, 20, 30, Over Current Ranges : Start With OFF then 4A TO 480A of IR (Rated Current) Step Size : 1A |
Time Setting |
Over Current Trip Time: 0 - 999sec, Under Current Ranges : Start With OFF then 1A TO 79A, Of IR (Rated Current) Step Size : 1A, Under Current Trip Time: 0 - 999sec, Current Asymmetry Ranges : Start With OFF then 1A TO (Ir-1)A, Of IR (Rated Current) Step Size : 1A, Current Asymmetry Trip time: 0 - 999sec, Locked current / Stall current: (Ir+1)A to 60A(Default :20A), (Ir+1)A to 240A(Default : 80A), (Ir+1)A to 480A(Default: 160A) Step Size : 1A, Locked Current Trip time: 0 - 999sec, Earth Fault Ranges : Start With OFF then 1A TO 160A, Step Size : 1%, Earth Fault Trip time: 0 - 999sec, Phase Loss trip time: Instantaneous, Phase Reversal Trip time: Instantaneous |
Auto Restart Attempt Time Frame | 0 - 999sec for Current related parameter, 0 - 999sec for EFR |
Mounting | Panel Mount |
Size | 96 X 96mm |
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping & Delivery Policy: |
1. | 100 INR will be charged as shipping fee if buyer and seller are from same city. If Buyer and Seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |
3. | Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis |
4. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |