Relay interface module low-volt in-built | BOSCH
Product Name | Relay interface module low-volt in-built | BOSCH |
---|---|
Weight | 1.000000 |
COUNTRY OF MANUFACTURE | India |
Brand | Bosch |
HSN Code | 8536 |
System Type | CONVENTIONAL |
Model | FLM-420-RLV1-E |
Freight | To pay by Customer, extra at actuals. Godown Delivery |
Category | Alarm System, Fire Safety, Control Module |
Product Code | CPK-0047 |
• FLM‐420‐RLV1 Relay Interface Modules Low Voltage
• Maximum switching current of 5 A (type DIN rail) /1 A (type in-built)
• Low current consumption
• Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators
The FLM‐420‐RLV1 Relay Interface Modules Low Voltage feature a changeover contact relay for providing a potential-free output contact.They are 2‐wire LSN elements. When connected to the fire panels FPA‐5000 and FPA‐1200, the interface module offers the enhanced functionality of LSN improved technology.
System Overview
Description | Connection |
REL1 NC | COM | NO | Relay (NC, COM and NO contact) |
LSN b1+ | a- | b2+ | LSN (in/out) |
REL1 COM | NO | NC | REL1 COM | NO | NC |
LSN SHIELD | Shielding cable (if available) |
LSN POWER 0 V | 0 V | +24 V | +24 V |
LSN power supply (supports for looping through) |
LSN a1- | b1+ | a2- | b2+ | LSN (in/out) |
Functions
The addresses of the interface modules are set using:
• DIP switches for FLM‐420‐RLV1‐E
• Rotary switches for FLM‐420‐RLV1‐D.
When connecting to the FPA-5000 Modular Fire Panel (LSN mode improved version), the operator can select automatic or manual addressing with or without auto-detection. In LSN mode classic, connection to the fire panels BZ 500 LSN, UEZ 2000 LSN and UGM 2020 is possible.
Address rotary switches | Address DIP switches | Operating mode |
0 0 0 | 0 |
Loop/stub in improved version LSN mode with automatic addressing (T- |
0 0 1 - 2 5 4 |
1 - 254 | Loop/stub/T-taps in improved version LSN mode with manual addressing |
CL 0 0 | 255 | Loop/stub in LSN mode classic |
LSN features
Integrated isolators ensure that function is maintained in the event of a short circuit or line interruption in the LSN loop. A fault indication is sent to the fire panel.
Features of LSN improved version
The interface modules in the 420 series offer all the features of improved LSN technology:
• Flexible network structures including T‐tapping without additional elements
• Up to 254 LSN improved elements per loop or stub line
• Unshielded cable can be used
• Downwards compatible with existing LSN systems and control panels.
Interface variants
The input interface modules are available in various designs:
• FLM‐420‐RLV1‐E type in-built:
- Can be built in to standard device boxes in accordance with EN 60670
- For space-saving installation in devices
• FLM‐420‐RLV1‐D type DIN rail:
- For installation on a DIN rail in accordance with EN 60715 with included adapter
- Can be built in to a FLM‐IFB126‐S surface-mounted housing.
Certifications and Approvals
Complies with
• EN54-17:2005
• EN54-18:2005
Region | Certification | |
Germany | VdS | G 207077 FLM-420-RLV1-D; FLM-420- RLV1-E; FLM-420-RLV1-W |
CE | FLM-420-RLV1-E FLM-420-RLV1-D |
|
CPD | 0786-CPD-20291 FLM-420-RLV1 0786-CPD-20292 FLM-420-RLV1-W, -E |
Installation/Configuration Notes
• Can be connected to the fire panels FPA‐5000 and FPA‐1200 and the classic LSN fire panels BZ 500 LSN, UEZ 2000 LSN and UGM 2020.
• Programming is done with the programming software of the fire panel.
• The connected device must have a minimum activation time of 20 ms.
• The LSN connection is established via the two wires on the LSN line.
• The in-built (-E) version is fitted with terminals to allow a second wire pair to be looped through to the LSN power supply of subsequent elements.
• For a fire system operation according to EN 54‐2, the interface modules used for the activation of fire protection equipment and whose outputs are not monitored, must be installed directly next to or within the device which shall be activated.
Parts Included
Type | Qty. | Component |
FLM-420-RLV1-E | 1 |
Relay Interface Module Low Voltage, type in-built |
FLM-420- RLV1-D | 1 |
Relay Interface Module Low Voltage, type DIN rail, with adapter and light pipe |
Technical Specifications
Electrical
LSN | |
• LSN input voltage | 15 V DC to 33 V DC (min. to max.) |
• Max. current consump- tion from LSN |
1.75 mA |
Relay (low voltage) | Normally closed, common and normally open contact (NC/COM/NO) |
Contact load (ohm resistive load) FLM‐420‐RLV1‐E | |
• Max. switching current | 1 A |
• Max. switching voltage | 30 V DC |
• Min. switching current | 0.01 mA |
• Min. switching voltage | 10 mV DC |
Contact load (ohm resistive load) FLM‐420‐RLV1‐D | |
• Max. switching current | 5 A |
• Max. switching voltage | 30 V DC |
• Min. switching current | 0.1 mA |
• Min. switching voltage | 100 mV DC |
Minimum activation time of the connected device | > 20 ms |
Mechanical
Connections | |
• FLM-420-RLV1-E | 12 screw terminals |
• FLM-420-RLV1-E | 12 screw terminals |
Permitted wire cross-section | |
• FLM-420-RLV1-E | 0.6 to 2.0 mm2 |
• FLM-420-RLV1-D | 0.6 to 2.0 mm2 |
Address setting | |
• FLM-420-RLV1-E | 8 DIP switches |
• FLM-420- RLV1-D | 3 rotary switches |
Housing material | |
• FLM-420- RLV1-E | ABS/PC blend |
• FLM-420- RLV1-D withadapter | PPO (Noryl) |
Color | |
• FLM-420- RLV1-E | Signal white, RAL 9003 |
• FLM-420- RLV1-E | Off-white, similar to RAL 9002 |
Dimensions | |
• FLM-420- RLV1-E | Approx. 50 mm x 22 mm (Ø x H) |
• FLM-420- RLV1-D with adapter |
Approx. 110 x 110 x 48 mm (W x H x D) |
Weight | Without / with packaging |
• FLM-420- RLV1-E | Approx. 35 g / 130 g |
• FLM-420- RLV1-D | Approx. 150 g / 235 g |
Environmental conditions
Permitted operating tempera- ture |
-20 °C to +55 °C |
Permitted storage temperature | -25 °C to +80 °C |
Permitted rel. humidity | < 96% (non-condensing) |
Classes of equipment as per IEC 60950 |
Classes of equipment as per IEC 60950 |
Protection class as per IEC 60529 |
Protection class as per IEC 60529 |
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping & Delivery Policy: |
1. | 100 INR will be charged as shipping fee if buyer and seller are from same city. If Buyer and Seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |
3. | Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis |
4. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |