Relay interface module low-volt in-built | BOSCH

₹2,954.00 ₹3,485.72
In stock
More Information
Product NameRelay interface module low-volt in-built | BOSCH
Weight1.000000
COUNTRY OF MANUFACTUREIndia
BrandBosch
HSN Code8536
System TypeCONVENTIONAL
ModelFLM-420-RLV1-E
Freight To pay by Customer, extra at actuals. Godown Delivery
CategoryAlarm System, Fire Safety, Control Module
Product CodeCPK-0047
Freight Extra (Godown Delivery)
In Stock ( 100 Units )

• FLM‐420‐RLV1 Relay Interface Modules Low Voltage

• Maximum switching current of 5 A (type DIN rail) /1 A (type in-built)
• Low current consumption
• Maintains LSN loop functions in the event of wire interruption or short-circuit     thanks to two integrated isolators

The FLM‐420‐RLV1 Relay Interface Modules Low Voltage feature a changeover contact relay for providing a potential-free output contact.They are 2‐wire LSN elements. When connected to the fire panels FPA‐5000 and FPA‐1200, the interface module offers the enhanced functionality of LSN improved technology.

System Overview

Description Connection
REL1 NC | COM | NO Relay (NC, COM and NO contact)
LSN b1+ | a- | b2+ LSN (in/out)
REL1 COM | NO | NC REL1 COM | NO | NC
LSN SHIELD Shielding cable (if available)
LSN POWER
0 V | 0 V | +24 V | +24 V
LSN power supply (supports for looping
through)
LSN a1- | b1+ | a2- | b2+ LSN (in/out)

Functions

The addresses of the interface modules are set using:
    • DIP switches for FLM‐420‐RLV1‐E
    • Rotary switches for FLM‐420‐RLV1‐D.
When connecting to the FPA-5000 Modular Fire Panel (LSN mode improved version), the operator can select automatic or manual addressing with or without auto-detection. In LSN mode classic, connection to the fire panels BZ 500 LSN, UEZ 2000 LSN and UGM 2020 is possible.

Address rotary switches Address DIP switches Operating mode
0 0 0 0

Loop/stub in improved version LSN

mode with automatic addressing (T-
taps not possible)

0 0 1
-
2 5 4
1 - 254 Loop/stub/T-taps in improved version
LSN mode with manual addressing
CL 0 0 255 Loop/stub in LSN mode classic

LSN features

Integrated isolators ensure that function is maintained in the event of a short circuit or line interruption in the LSN loop. A fault indication is sent to the fire panel.

Features of LSN improved version
The interface modules in the 420 series offer all the features of improved LSN technology:
• Flexible network structures including T‐tapping without additional                  elements
• Up to 254 LSN improved elements per loop or stub line
• Unshielded cable can be used
• Downwards compatible with existing LSN systems and control panels.

Interface variants

The input interface modules are available in various designs:
•  FLM‐420‐RLV1‐E type in-built:
      - Can be built in to standard device boxes in accordance with EN 60670
      - For space-saving installation in devices
• FLM‐420‐RLV1‐D type DIN rail:
     - For installation on a DIN rail in accordance with EN 60715 with included         adapter

    - Can be built in to a FLM‐IFB126‐S surface-mounted housing.

Certifications and Approvals

Complies with
• EN54-17:2005
• EN54-18:2005

Region   Certification
Germany VdS G 207077 FLM-420-RLV1-D; FLM-420-
RLV1-E; FLM-420-RLV1-W
  CE FLM-420-RLV1-E
FLM-420-RLV1-D
  CPD 0786-CPD-20291 FLM-420-RLV1
0786-CPD-20292 FLM-420-RLV1-W, -E

Installation/Configuration Notes

• Can be connected to the fire panels FPA‐5000 and FPA‐1200 and the classic     LSN fire panels BZ 500 LSN, UEZ 2000 LSN and UGM 2020.
• Programming is done with the programming software of the fire panel.
• The connected device must have a minimum activation time of 20 ms.
• The LSN connection is established via the two wires on the LSN line.
• The in-built (-E) version is fitted with terminals to allow a second wire pair     to be looped through to the LSN power supply of subsequent elements.
• For a fire system operation according to EN 54‐2, the interface modules          used for the activation of fire protection equipment and whose outputs are      not monitored, must be installed directly next to or within the device which    shall be activated.

Parts Included

Type Qty. Component
FLM-420-RLV1-E 1

Relay Interface Module Low Voltage, type in-built

FLM-420- RLV1-D 1

Relay Interface Module Low Voltage, type

DIN rail, with adapter and light pipe

Technical Specifications

Electrical

LSN  
• LSN input voltage 15 V DC to 33 V DC (min. to max.)
• Max. current consump-
tion from LSN
1.75 mA
Relay (low voltage) Normally closed, common and normally
open contact (NC/COM/NO)
Contact load (ohm resistive load) FLM‐420‐RLV1‐E
• Max. switching current 1 A
• Max. switching voltage 30 V DC
• Min. switching current 0.01 mA
• Min. switching voltage 10 mV DC
Contact load (ohm resistive load) FLM‐420‐RLV1‐D
• Max. switching current 5 A
• Max. switching voltage 30 V DC
• Min. switching current 0.1 mA
• Min. switching voltage 100 mV DC
Minimum activation time of the connected device > 20 ms

Mechanical

Connections
•   FLM-420-RLV1-E 12 screw terminals
•   FLM-420-RLV1-E 12 screw terminals
Permitted wire cross-section
•   FLM-420-RLV1-E 0.6 to 2.0 mm2
•   FLM-420-RLV1-D 0.6 to 2.0 mm2
Address setting
•  FLM-420-RLV1-E 8 DIP switches
•  FLM-420- RLV1-D 3 rotary switches
Housing material
•  FLM-420- RLV1-E ABS/PC blend
•  FLM-420- RLV1-D withadapter PPO (Noryl)
Color
•  FLM-420- RLV1-E Signal white, RAL 9003
•  FLM-420- RLV1-E Off-white, similar to RAL 9002
Dimensions
•  FLM-420- RLV1-E Approx. 50 mm x 22 mm (Ø x H)
•  FLM-420- RLV1-D with
adapter
Approx. 110 x 110 x 48 mm (W x H x D)
Weight Without / with packaging
•  FLM-420- RLV1-E Approx. 35 g / 130 g
•  FLM-420- RLV1-D Approx. 150 g / 235 g

Environmental conditions

Permitted operating tempera-
ture
-20 °C to +55 °C
Permitted storage temperature -25 °C to +80 °C
Permitted rel. humidity < 96% (non-condensing)
Classes of equipment as per
IEC 60950
Classes of equipment as per
IEC 60950
Protection class as per
IEC 60529
Protection class as per
IEC 60529

 

Returns Policy:
1. Once orders are placed, cancellations are not permitted.
2.  Payments for orders will not be adjusted or refunded in case of cancellation.
Shipping Policy:
1. Material will be shipped exclusively on a To-Pay basis for Godown Delivery only.
2.  Shipping freight costs will be additional and based on actuals, to be borne by the buyer.
3. Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis
Write Your Own Review
You're reviewing:Relay interface module low-volt in-built | BOSCH
Your Rating
WA button WA button