Output-input Interface Module | BOSCH
Product Name | Output-input Interface Module | BOSCH |
---|---|
Weight | 1.000000 |
COUNTRY OF MANUFACTURE | India |
Brand | Bosch |
HSN Code | 85389000 |
System Type | CONVENTIONAL |
Model | FLM‑420‑O1I1 |
Freight | To pay by Customer, extra at actuals. Godown Delivery |
Category | Alarm System, Fire Safety, Control Module |
Product Code | CPK-0030 |
FLM‐420‐O1I1 Output-input Interface Modules
• Semi-conductor output electrically isolated from LSN loop and short-circuit proof
• Max. switchable current per output 700 mA
• Individually selectable input monitoring functions (EOL or contact)
• Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators
The FLM‐420‐O1I1 Output-input Interface Modules are fitted with one output to control external devices and with one monitored input. They are 2‐wire LSN elements for connection to the fire panels FPA‐5000 and FPA‐1200 and offer the enhanced functionality of LSN improved technology.
Functions
The semi-conductor output is electrically isolated from the LSN loop and protected against short circuits.
Output power supply
The power supply for loads connected to the output can be selected as:
• Auxiliary power supply from the fire panel
• Or, for FLM‐420‐O1I1-D only: External power supply units
Input monitoring functions
The FLM‐420‐O1I1 Output-input-Interface Module provides two monitoring functions:
1. Monitoring of a line by an EOL resistor
2. Monitoring of a potential‐free contact The input monitoring functions can be selected by setting the corresponding addresses.
1. Monitoring of a line by an EOL resistor
2. Monitoring of a potential‐free contact
The input monitoring functions can be selected by setting the corresponding addresses.
Line monitoring with EOL resistor
The EOL resistor has a standard resistance of 3.9 kΩ.
The interface module detects
• Standby
• Triggering in the event of a short circuit
• Triggering in the event of line interruption
Position | Description |
RΣ | Overall line resistance with RΣ = RL/2 + RL/2 + REOL |
RL/2 | Line resistance |
The following line conditions will be reliably detected
if the overall line resistance is within the specified
range:
Line condition | Overall line resistance R Σ |
Standby | 1500 Ω to 5500 Ω |
Short circuit | < 800 Ω |
Interruption | > 85000 Ω |
Contact monitoring
The interface module evaluates the operating conditions "open" or "closed". The normal operating condition can be programmed for each input. Contact
monitoring has a pulse intensity of 8 mA.
Adress switches
The address of the interface module is set using:
• DIP switches in case of the FLM‐420‐O1I1‐E
• Rotary switches in case of the FLM‐420‐O1I1‐D
In improved version LSN mode, the operator can select automatic or manual addressing with or without auto-detection.
Address rotary switches |
Address DIP switches |
Mode |
0 0 0 | 0 |
Loop/stub in improved version LSN mode with automatic addressing (T-taps not pos- |
0 0 1 - 2 5 4 |
1 - 254 | Loop/stub/T-taps in improved version LSN mode with manual addressing |
CL 0 0 | 255 | Loop/stub in LSN mode classic |
LSN features
Integrated isolators ensure that function is maintained
in the event of a short circuit or line interruption in
the LSN loop. A fault indication is sent to the fire
panel.
Features of LSN improved version
The interface modules in the 420 series offer all the
features of improved LSN technology:
• Flexible network structures including T‐tapping
without additional elements
• Up to 254 LSN improved elements per loop or stub line
• Unshielded cable can be used
Interface variants
The Output-input Interface Modules are available in
various designs:
• FLM‐420‐O1I1‐E in-built version:
– Suitable for standard device boxes according to EN 60670 and
– For a space-saving installation in all devices
• FLM‐420‐O1I1‐D DIN-rail version:
– Suitable for installation on a DIN-rail according to EN 60715 with included adapter and
– For the FLM‐IFB126‐S surface-mounted housing
Complies with
• EN 54-17: 2005
• EN 54-18: 2005 + AC:2007
Region | Regulatory compliance/quality marks | |
Germany | VdS | G 209070 FLM-420-O1I1-E |
VdS | G 209069 FLM-420-O1I1-D | |
Europe | CE | FLM-420-O1I1-E |
CE | FLM-420-O1I1-D | |
CPD | 0786-CPD-20714 FLM-420-O1I1-E | |
CPD | 0786-CPD-20715 FLM-420-O1I1-D | |
Hungary | TMT | TMT-36/2010 szamu FLM-420-O8I2-S, FLM-420-O1I1-E, FLM-420-O1I1-D, FLM-420-RLE-S |
Ukraine | MOE | UA1.016.0070232-11 FLM-420-O1I1-E |
MOE | UA1.016.0070232-11 FLM-420-O1I1-E |
Description | Connection | |
IN | IN- | IN+ | Input 1 |
OUT | POW+ | Reference potential (+) |
OUT- | Output (switched negative potential) | |
POWER IN | POW+ | 0V | Power supply output |
LSN | b1+ | a- | b2+ | LSN (incoming / outgoing) |
POWER IN | POW+ | 0V- |
Power supply (interface module and output) |
OUT | POW+ | Reference potential (+) |
OUT- | Output (switched negative potential) | |
IN | - | + | Input |
LSN | SHIELD | Cable shielding (if available) |
0V | +U | +U | Auxiliary power supply (support points to loop through) |
|
LSN | b2+ | a2- | b1+ | a1- | LSN (incoming / outgoing) |
• Can be connected to fire panels of LSN improved bus technology.
• Programming is done with the programming software of the fire panel.
• The LSN connection is established by the two wires of the LSN line.
• The power supply for the output is either fed by the auxiliary power supply
from the fire panel or by an external power supply unit.External power
supplies, for FLM‐420‐O1I1-D only, must be free-of-ground.
• The outputs OUT/OUT- are switched against the negative potential of the interface module (POWER IN/0V). The positive potential (OUT/POW+)is either supplied by the auxiliary power (AUX) from the fire panel or by an external power supply unit.
• The maximum switchable voltage of the semi-conductor output is 30 V DC. The maximum switchable current is 700 mA (depending on the external power supply).
• The activation of the input IN has to be carried out electrically isolated from LSN (e.g. with relay contacts, pushbutton, etc.).
• The input must have a minimum activation time of 3.2 s.
• For FLM‐420‐O1I1-D applies: A maximum cable length of 3 m is permitted per input and output. FLM‐420‐O1I1-E must be mounted flush with the
connected device.
• The maximum cable length of all inputs connected to the loop or stub is 500 m in total. Additionally, all outputs which are not electrically isolated from LSN must be included in the total line length calculation (e.g. peripherals connected via C points). With UEZ 2000 LSN and UGM 2020, the limitation to
500 m applies to each Network Processing Converter (NVU).
• The interface module has terminals blocks to allow a second pair of wires to be looped through to supply the downstream connected elements with LSN power.
• For a fire system operation according to EN 54‐2, the interface modules used for the activation of fire protection equipment and whose outputs are not monitored, must be installed directly next to or
within the device which shall be activated.
Technical specifications
Electrical | |
LSN | |
• LSN input voltage | 15 V DC to 33 V DC |
• Max. current consumption from LSN |
1.9 mA |
Output | |
• Max. switchable voltage of semi-conductor output |
30 V DC |
• Max. switchable output current |
700 mA (depending on power supply) |
Input | |
Line monitoring with EOL | |
• EOL resistor | Nominal 3.9 kΩ |
• Overall line resistance RΣ with RΣ = RL/1 + RL/2 + REOL |
• Standby: 1500 Ω to 5500 Ω • Short circuit: < 800 Ω • Line interruption: > 85000 Ω |
Contact monitoring | |
• Max. current strength (current pulse) |
8 mA |
Minimum activation time of the in- put |
3.2 s |
Mechanical | |
Connections | |
• FLM-420-O1I1-E | 14 screw terminals |
• FLM-420-O1I1-D | 12 screw terminals |
Permissible wire diameter | |
• FLM-420-O1I1-E | 0.6 mm2 to 2.0 mm2 |
• FLM-420-O1I1-D | 0.6 mm2 to 3.3 mm2 |
Address setting | |
• FLM-420-O1I1-E | 8 DIP switches |
• FLM-420-O1I1-D | 3 rotary switches |
Housing material | |
• FLM-420-O1I1-E | ABS/PC blend |
• FLM-420-O1I1-D incl. adapter |
PPO (Noryl) |
Housing color | |
• FLM-420-O1I1-E | Signal white, RAL 9003 |
• FLM-420-O1I1-D incl. adapter |
Gray white, similar to RAL 9002 |
Dimensions | |
• FLM-420-O1I1-E | Approx. 50 mm x 22 mm (Ø x H) |
• FLM-420-O1I1-D incl. adapter |
Approx. 110 x 110 x 48 mm (W x H x D) |
Weight | Without/with packing |
• FLM-420-O1I1-E | Approx. 35 g / 170 g |
• FLM-420-O1I1-D | Approx. 95 g / 390 g |
Environmental conditions | |
Permissible operating temperat- ure |
-20 °C to +65 °C |
Permissible storage temperature | -25 °C to +80 °C |
Permissible rel. humidity | < 96% (non-condensing) |
Classes of equipment as per IEC 60950 |
Class III equipment |
Protection class as per IEC 60529 | IP 30 |
System limiting values | |
System limiting values | |
• FLM-420-O1I1-D | 3 m |
• FLM-420-O1I1-E | Flush mounted |
Maximum cable length output | |
• FLM-420-O1I1-D | 3 m |
• FLM-420-O1I1-E | Flush mounted |
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping & Delivery Policy: |
1. | 100 INR will be charged as shipping fee if buyer and seller are from same city. If Buyer and Seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |
3. | Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis |
4. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |