Product NameFire Alarm Heat Detector | Conventional Thermal Detector | Siemens
Weight1.000000
COUNTRY OF MANUFACTUREIndia
BrandSiemens
HSN Code85311090
System TypeCONVENTIONAL
ModelHI121
Freight To pay by Customer, extra at actuals. Godown Delivery
CategoryAlarm System, Fire Safety, Detectors, Heat Detectors
Product CodeCPK-0034
Freight Extra (Godown Delivery)
In Stock ( 100 Units )

Magnet-test feature

Incorporates one (1) state-of-the- art thermal sensor for uniform response and positioning

Available optional sounder base, providing an alert and evacuation signal

UL 521 Listed, ULC S530 Listed

FM, CSFM Approved

Model HI121 from Siemens ─ Fire Safety is a thermal detector that comes with a new magnet-test feature. The magnet-test feature allows for Model HI121 to be tested without the use of a heat gun, providing quick testing for installers and test personnel to prove the integrity of the wiring and proper connection to the fire alarm control panel (FACP).

An indication of supervision status is provided by Siemens Fire’s unique (3) three- color light-emitting diode (LED) provided locally on the detector ─ and optionally with the various remote LED indicators.

Environmental Ratings
OPERATING TEMPERATURE: 32°F (0°C) ─ 100°F (38°C)
HUMIDITY: 0 – 95% (non-condensing)
ALARM TEMPERATURE: 135oF (57oC)
AIR PRESSURE: No Effect
AIR VELOCITY: 0 ─ 4000 feet / minute [for open-area protection and direct, in-duct application]

 

Electrical Ratings
VOLTAGE: 16VDC – 27VDC
RIPPLE: 3V (peak to peak)
SUPERVISORY CURRENT: 100μA
ALARM CURRENT: 50mA
START-UP TIME: 30 seconds, max.

 

LED Indicator Operation
FLASH COLOR CONDITION FLASH INTERVAL
GREEN Normal supervisory operation. 10
YELLOW Detector is in trouble and needs replacement. 5
RED Alarm condition. 2.5
NO FLASH Detector is not powered, or detector requires repair. --

 

Returns Policy:
1. Once orders are placed, cancellations are not permitted.
2.  Payments for orders will not be adjusted or refunded in case of cancellation.
Shipping Policy:
1. Material will be shipped exclusively on a To-Pay basis for Godown Delivery only.
2.  Shipping freight costs will be additional and based on actuals, to be borne by the buyer.
3. Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis
Write Your Own Review
You're reviewing:Fire Alarm Heat Detector | Conventional Thermal Detector | Siemens
Your Rating
WA button WA button