Architect & Engineer Specifications
Sophisticated series of notification appliances that meets fire-industry codes
and regulations for commercial-building applications
• Compatible with the Siemens 50-point, 252-point and 504-point addressable fire alarm control panels (FACPs), and with:
- Siemens Modular FACPs
- Siemens PAD-series of NAC extenders
- FireFinder® XLS / XLSV FACPs
- Siemens dual-sync control (DSC) modules
• Innovative LED strobe technology provides an energy-efficient means for a
significantly reduced current draw
- Capability to have existing Xenon and new LED strobes in the same field-of-view
- Fewer power supplies required, smaller wire gage, reduced wire runs
• Straightforward installation coupled with compact, modern design
- No visible mounting screws
- Manual (index finger) slide-setting adjustor
- Four (4) field-selectable settings in one (1) device: 15cd | 30cd | 75cd |110cd
• Faceplates ship in four (4) distinctive types:
- ‘FIRE’ | ‘ALERT’ | ‘AGENT’ | (blank)
• Two (2) audible settings in each notification appliancev
- Temporal or steady horn output
- High or Low setting
• UL (2034 | 1971 | 464) and ULC Listed (ULC-S525 | - S526) ; CS
• ADA | NFPA | FCC | ANSI | OSHA compliant
Product Overview
Formed as the `SL’-series, Siemens is now offering horns, strobes, and horn-strobes with LED based strobes to its notification-appliances portfolio. With the `SL’-series, Siemens offers a full range of products with low and high candela settings that makes these sophisticated notification appliances ideal for new installs and retrofit applications.
Innovative light-emitting diode (LED) strobe technology provides an energy-efficient means for a significantly reduced current draw.The strobe portion of these appliances meets the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. This feature allows existing Xenon and the new LED devices to be used in the same field-of-view.
In a single device, the `SL’-series can provide alarm-signaling tones for dual
applications. All strobe models in the series feature multi-Candela settings (15 | 30 | 75 | 110cd) on a single appliance.
Additionally, there are two (2) modes of operation for the audible portion of these notification appliances:
• T3 (coded)
• Continuous
The `SL’-series of horns, strobes and horn-strobes devices are produced in a sleek,modern design. Its single-gang form factor provides high-quality energy efficiency in an aesthetically pleasing, low-profile design that is consistent to the look of the interior composition of the building application.
The `SL’-series is apt for indoor wall-mount applications. The Model `SLH’-series horn appliances work in either 12V or 24VDC, whereas the Series `SLSW’ and `SLHSW’ strobe and horn-strobe devices are specifically for 24V operation.
Specifications
In terms of composition and functionality, Models `SLHW’-series, `SLSW’-series, and `SLHSW’-series provide added value to the installer for the types of applications for operation:
• Compact | sleek | low-profile design
• Comprehensive feature list
• Convenient mounting options
• Easy-to-adjust selection-slider switch for Candela settings
− No tools required for setting changes
− Multi-level settings: 15cd | 30cd | 75cd | 110cd
• High and Low audible outputs
• Reduced current draw, via cutting-edge LED technology
The LED portions of the Siemens `SL’-series of strobes and horn-strobes meet the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. By meeting this latest requirement, existing Xenon as well as the new LED-technology devices can now be in the same field-of-view.
The horn, strobe and horn-strobes in this Siemens `SL’-series of notification appliances have received UL / ULC Listed status by attaining compatible testing standards with all of the Siemens fire-alarm control panels (FACPs) and accessories that have been determined to be aligned with existing Siemens strobe-based appliances.
This would include the following existing model-types: `CH’|`HS’|`MTH’ |`S-HQ’|`SA’|`SE’|`SEF’|`SET’ |`ST’ |`STH’ |`ZR’ and `ZH’ Series notification appliances. The regulatory listing also includes the capability for installing the
Siemens `SL’-series LED-based strobes in the same notification zone and field-of-view with any existing Siemens Notification Appliance Xenon-based strobes.
All types of these horns, strobes and horn-strobes are UL Listed (for indoor use under Standard 1971 and464), as well as ULC-S525|ULC-S526 Listed. The Siemens `SL’-series sounder-strobes also have ADA | RoHS and ICES approval.
Technical Data
Wall-Mount | Horn-Strobes | Output Current Draw
Current Ratings (HIGH dB | in Amps) 16.0 – 33.0VDC |
|||||
MODEL `SLHSW’ SERIES: |
Setting | 15cd | 30cd | 75cd | 110cd |
Code | 0.034 | 0.046 | 0.105 | 0.214 | |
Continuous | 0.042 | 0.052 | 0.110 | 0.217 |
Wall-Mount | Horn-Strobes | Output Current Draw
Current Ratings (LOW dB | in Amps) 16.0 – 33.0VDC |
|||||
MODEL `SLHSW’ SERIES: |
Setting | 15cd | 30cd | 75cd | 110cd |
Code 3 | 0.032 | 0.042 | 0.102 | 0.213 | |
Continuous | 0.036 | 0.044 | 0.104 | 0.216 |
GENERAL NOTES:
1. Strobes are designed to flash at 1-flash-per-second minimum over their “ Regulated Voltage Range.”
2. NFPA-72 specifies a flash rate of 1-to-2 flashes-per-second, and guidelines for the Americans with Disabilities Act (ADA)
specify a flash rate of 1-to-3 flashes-per-second.
3. All Candela ratings represent minimum effective Strobe intensity based on UL 1971.
Technical Data
…General Properties
OPERATING TEMPERATURE: |
- 32°F (0°C) to 122°F (50°C) - for indoor-applications’ use only |
RELATIVE HUMIDITY: | 93%, maximum |
OPERATING VOLTAGE RANGES: |
- 12 VDC / VFWR - 8 - 17.5 VDC / VFWR; - 24 VDC / VFWR - 16 - 33 VDC/VFWR (12 VDC for Model SLH Wonly) |
STROBE OUTPUT RATING: |
- UL 1971, ULC-S526 - Field-selectable 15cd | 30cd | 75cd | 110cd Candela outputs |
STROBE FLASH RATE: | Strobes are designed to flash at one-flash-per-second |
STROBE SYNCRONIZATION: |
- all Siemens addressable panels - Siemens PAD-series NAC extenders - Siemens dual-sync (DSC) modules, which provide the unique Siemens proprietary synchronization protocol |
TEMPORAL PATTERN: |
- Continuous - Code 3 (1/2 second on, 1/2 second off; then 1/2 second on, 1/2 second off; followed by 1/2 second on, 1-1/2 second off and repeat) NOTES: The Code 3 pattern is specified by ANSI and NFPA 72 for Standard Emergency Evacuation Signaling. |
Physical Properties
MODEL `SL’-series | |||
MATERIAL: | - White-or-red textured, ultraviolet (UV) stabilized, colored impregnated engineered plastic - Exceeds 94V-0 UL flammability rating |
||
WEIGHT: | 0.35 Lbs. (0.16 Kg.) | ||
LENS TYPE: | LED strobe situated in a rugged Lexan lens | ||
DIMENSIONS: |
|
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping Policy: |
1. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |