4 Zone Conventional Fire Alarm Control Panel, RE 104 | Ravel
Product Name | 4 Zone Conventional Fire Alarm Control Panel, RE 104 | Ravel |
---|---|
Weight | 1.000000 |
COUNTRY OF MANUFACTURE | India |
Brand | Ravel |
HSN Code | 8531 |
System Type | CONVENTIONAL |
Model | RE104 |
Freight | To pay by Customer, extra at actuals. Godown Delivery |
Category | Alarm System, Conventional System, Fire Safety |
Product Code | CPK-0084 |
• RE-104 Fire Alarm Control Panel
Product Overview
RE-104 is a right blend of affordable design and quality with latest technology for fire alarm control panels.This microprocessor based conventional Fire Alarm Control panel, is designed for small size commercial buildings and small scale industries. RE-104 model is an user friendly 4 zone standalone control panel, with optional zone wise Sounder/Contact respectively.
Special Features:
• Switched Mode Power Supply.
• Modular Construction, Serviceable.
• Surface Mount Technology.
• Battery polarity & deep discharge protection.
Features:
• As per IS -15908: 2011 Standard.
• 16 X 2 Dot Matrix LCD Display.
• Standby battery backup with built in charging.
• Fire / Fault status in unambiguous colored LED indication.
• Switch Mode Power Supply.
• Tactile Keypad for easy panal Operation.
• System ON indication.
• Main Standby status indication.
• Low Battery Visual warning with audible tone.
• Relay output for actuators,for Fire and Fault.
• Lamp Test facility.
• Zone wise one man Walk Test Facility.
• Zone wise lsolation facility with loop Voltage cut off.
• Compatible to all type of Conventional Detectors.
• Optional Zone Wise Sounder/Zone Wise Contact.
Electrical Specification:
Primary Power :- | 120 / 220VAC + 10% -15%, 60 / 50 Hz. 60W |
Standby Power :- |
24VDC (2 Nos of 12V, 7Ah Sealed Lead acid battery). Quiescent current : 55mA |
Operating Condition:- |
Operating Temperature - 0 - 49° C/32-120° F. Storage Temperature - 0 to 60 C Relative Humidity - 93 ± 2% RH (non- condensing) |
Charging Circuit:- |
Charging Voltage - 28.0V, ± 2%
|
Notification Appliance Circuits:- | Class B wiring Operating Nominal Voltage: 24VDC Current for NACs : 0.6 Amp End-Of-Line Resistor : 4K7, 1/4 watt |
Common Relays:- | Type : Form C No of Relays : 3 Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @125VAC. Power Factor : 1.0 |
Initiating Device Circuits (Zone Circuit):- |
All zones are Class B wiring (2.4mA for Detectors) |
Mechanical Specification:
Dimensions | : (350W X 250H X 100D) |
Color | : Red / White |
Construction | : 18 Gauge (1.22mm) CRCA sheet with powder-coated finish |
IP Rating | : IP50 |
Cable Entry | : 11xø19mm Knockout on top of the cabinet |
Returns Policy: |
1. | Once orders are placed, cancellations are not permitted. |
2. | Payments for orders will not be adjusted or refunded in case of cancellation. |
Shipping & Delivery Policy: |
1. | 100 INR will be charged as shipping fee if buyer and seller are from same city. If Buyer and Seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals. |
2. | Shipping freight costs will be additional and based on actuals, to be borne by the buyer. |
3. | Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis |
4. | Material will be shipped exclusively on a To-Pay basis for Godown Delivery only. |